Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker
Introduction: High Voltage Vacuum Circuit BreakerMZZ11-12/T630-20 Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker is an outdoor high voltage power distribution equipment which is of three-phase AC 50Hz 630A~1250A rated current 16kA~20kA short circuit current. It is mainly used in opening and closing load current, overload current and short circuit current in the power system. It is applied to the protection and control of the power distribution system in industrial mining enterprises as well as agriculture network and many other frequently used places. Having kept all reasonable parts and good performance of ZW32, it multiplies the overall mechanical life span including the arc chamber than the former model. Its life span can reach as high as sixty thousand times and thirty times free maintenance during the lifetime.
Working & Environmental Conditions - High Voltage Vacuum Circuit Breaker
1. Environmental temperature: -40°C~+55°CDiurnal temperature difference25°C
2. Altitude: Lower than 2000m
3. Wind Pressure: No more than 700 Pa (equal to wind speed of 35 m / s)
4. No regular dramatic shake, earthquake intensity < 8°
5. No strong corrosion gas , conductive media (such as various acids, large alkali, thick smoke)
6. Anti-filthy-capacity: Ⅳ
Model Meaning of High Voltage Vacuum Circuit Breaker

Main Technical Parameters - High Voltage Vacuum Circuit Breaker [Electrical Switch]
| Order | Name | Unit | Parameter | |
| 1 | Rated voltage | KV | 12 | |
| 2 | Rated current | A | 630/1250 | |
| 3 | Rated frequency | HZ | 50 | |
| 4 | 1min work frequency voltage tolerance | Dry test | KV | 42/49 |
| Wet test | 30 | |||
| 5 | Lightening impact current tolerance (peak value) alternated, towards the ground/fracture | KV | 75/85 | |
| 6 | Rated short circuit breaking current | KA | 20 | |
| 7 | Rated short circuit closing current (peak value) | KA | 50 | |
| 8 | Rated peak value current tolerance | KA | 50 | |
| 9 | 4S short term current tolerance | KA | 20 | |
| 10 | Rated operation cycle | Open-0.3S-close open-180S-close-open | ||
| 11 | Rated breaking times of short circuit current | Times | 3 | |
| 12 | Mechanical life span | Times | 50000 | |
| 13 | Secondary circuit 1min work frequency voltage tolerance | KV | 2 | |
| 14 | protective CT |
RATIO | A | ( )/5 |
| CAPACITY | VA | 12 | ||
| 15 | Weight | Kg | 100 | |
| Order | Name | Unit | Parameters |
| 1 | Contact openness size | Mm | 11±1 |
| 2 | Contact excess travel | Mm | 3+1.0 3-0.3 |
| 3 | Average Switch closing time | M/s | 0.65±0.15 |
| 4 | Average Switch opening time | M/s | 1.1±0.2 |
| 5 | Time differences of three-phase closing switch in the same period | Ms | ≤2 |
| 6 | Switch closing and bouncing time | Ms | ≤2 |
| 7 | Switch closing time | Ms | ≤60 |
| 8 | Switch opening time | Ms | ≤70 |
| 9 | Direct current resistance of each circuit phase | μΩ | ≤200 |
| 10 | Dynamic, stable contact allowed accumulated attrition thickness | Mm | 3 |
Picture 1: Contour and Installation Dimensions of ZW32-12/M630-201 Insulated cylinder 2 Vacuum arc chamber (in the cylinder) 3 Hoist ring 4 Switch handle 5 Energy storage handle6 The cabinet
7 permanent magnetic actuator(inside the cabinet) 8 open/close switch guides 9 Aviation plug 10 Current Transformer
Picture 2: Contour and Installation Dimensions of MZW32-12/M630-20 (attached isolated switch)1 Isolated knife 2 Insulated bar 3 Insulator 4 Static contact 5 isolated switch support
6 Isolated switch actuator handle 7 Isolated switch support 8 Interlock bar
Back


Complete set switchgear-Power Control System


