High Voltage Electric Components - AC High Voltage Vacuum Circuit Breaker

High Voltage Vacuum Circuit Breaker

Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker

Introduction: Outdoor High Voltage Vacuum Circuit Breaker 
MZZ10-12/T630-20 Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker is outdoor high voltage power distribution equipment which is of three-phase AC 50Hz 12kV rated voltage. It is mainly used in opening and closing load current, overload current and short circuit current in the power system. It is applied to the protection and control of the power distribution system in substations, industrial mining enterprises as well as agriculture network and many other frequently used places. If combined with the controller, it can meet the requirements of automatic power distribution system and reliably and efficiently function as the traditional recloser.
Working & Environmental Conditions - High Voltage Vacuum Circuit Breaker
1. Environmental temperature: -40°C~+55°CDiurnal temperature difference25°C
2. Altitude: Lower than 2000m
3. Wind Pressure: No more than 700 Pa (equal to wind speed of 35 m / s)
4. No regular dramatic shake, earthquake intensity < 8°
5. No strong corrosion gas , conductive media (such as various acids, large alkali, thick smoke)
6. Anti-filthy-capacity: Ⅳ
Model Meaning

Main Technical Parameters of High Voltage Vacuum Circuit Breaker
Order Name Unit Parameter
1 Rated voltage KV 12
2 Rated current A 630
3 Rated frequency HZ 50
4 1min work frequency voltage tolerance Dry test KV 42/49
Wet test 34
5 Lightening impact current tolerance (peak value) alternated, towards the ground/fracture KV 75/85
6 Rated short circuit breaking current KA 20
7 Rated short circuit closing current (peak value) KA 50
8 Rated peak value current tolerance KA 50
9 4S short term current tolerance KA 20
10 Rated operation cycle   Open-0.3S-close open-180S-close open
11 Rated breaking times of short circuit current Times 3
12 Mechanical life span Times 50000
13 Secondary circuit 1min work frequency voltage tolerance KV 2
14 Protective CT RATIO A ( )/5
CAPACITY VA 15
15 Weight Kg 180

Order Name Unit Parameter
1 Contact openness size Mm 11±1
2 Contact excess travel Mm 3+1.0 3-0.3
3 Average Switch closing time M/s 0.65±0.15
4 Average Switch opening time M/s 1.1±0.2
5 Time differences of three-phase closing switch in the same period Ms ≤2
6 Switch closing and bouncing time Ms ≤2
7 Switch closing time Ms ≤60
8 Switch opening time Ms ≤70
9 Direct current resistance of each circuit phase μΩ ≤200
10 Dynamic, stable contact allowed accumulated attrition thickness Mm 3
Contour & Installation Dimensions - Outdoor High Voltage Vacuum Circuit Breaker

Picture 1  Contour and Installation Dimensions of the Circuit Breaker
Picture 2  Structure, Contour and Installation Dimensions of the Combined Circuit Breaker
1 contact blade   2 contact    3    insulated bar  4   pillar
5 isolated switch actuator handle  6  shaft   7 Isolated switch support  8 circuit breaker