High Voltage Electric Components - High Voltage Vacuum Load Switch

Indoor High Voltage Vacuum Load Switch

Indoor High Voltage Vacuum Load Switch

Introduction: High Voltage Vacuum Load Switch [Vacuum Circuit Breaker]  
MZF62-12D/T630-20 Indoor High Voltage Vacuum Load Switch is applied to the power system of 50Hz three-phase AC 12kV rated voltage. It is capable of opening and closing, loading, breaking load and overloading current. It also can break and close the unloaded lone wires, transformers and capacitors.
MZF62-12D/T630-20 Indoor High Voltage Vacuum Load Switch-Fuse Combined Electrical Appliance is composed of this load switch and fuse. Besides the above functions it also has protective function.
working and Environmental Conditions - Indoor High Voltage Vacuum Load Switch
1. Environmental temperature: maximum temperature +40°C, minimum temperature -25°C
2. Altitude: Lower than 1000m
3. Environmental humidity:
- Daily average relative humidity: ≤95%
- Monthly relative humidity: ≤90%
4. No conductive dust, corrosion gas or steam. 
5. No fire or explosion danger
6. No dramatic shock
7. Gradient <3°
Model Meaning

Technical parameters - Indoor High Voltage Vacuum Load Switch
Order Item Unit Data
1 Rated voltage kv 12
2 Rated frequency Hz 50
3 Rated current A 630
4 Rated load breaking current A 630
5 Rated closed-loop breaking current A 630
6 5%rated load breaking current A 31.5
7 Rated electric charged current A 10
8 Rated unloaded transformer capacity KV/A 1250
9 1min
working frequency voltage tolerance(vacuum fracture, opposite direction, towards the ground, isolated fracture )
KV 42/48
10 Lightening impact voltage tolerance: (vacuum fracture, opposite direction, towards the ground, isolated fracture ) KV 75/85
11 Rated short term current tolerance (thermal stable) KA/S 20/4
12 Rated peak value current tolerance (dynamic stable) KA 5
13 Rated short circuit closing current KA 50
14 Mechanical life span Times 10000
15 Vacuum arc chamber allowed attrition thickness Mm 2
16 Operation voltage of power supply AC/DC V 110 , 220
Technical parameters - Combined electrical appliance
Order Item Unit Data
1 Rated voltage KV 12
2 Rated frequency HZ 50
3 Maximum rated current of the fuse A 125
4 Stable breaking alternating current A 3150
5 Time of Switch opening caused by the fuse Ms 40±5
6 Rated short circuit breaking current (RMS) KA 31.5
7 Rated short circuit breaking current (peak value) KA 50
8 1min
working frequency voltage tolerance(vacuum fracture, opposite direction, towards the ground, isolated fracture )
KV 42/48
9 Lightening impact voltage tolerance: (vacuum fracture, opposite direction, towards the ground, isolated fracture ) KV 75/85
10 Fuse impact energy output J 2-5
Contour & Installation Dimensions - High Voltage Vacuum Load Switch 1 framework 2 isolated knife 3 fuse 4 insulated bar 5 upper support 6 vacuum arc chamber 7 static contact 8 Insulator
9 grounded knife 10 ground spring 11 switch spring 12 release transmission gear 13 Insulated bar 14 Spindle 15 axis
16 regulation bar 17 spring actuator
pdfMZF62-12D/T630-20 Indoor High Voltage Vacuum Load Switch