High Voltage Electric Components - High Voltage Load Switch

Indoor High Voltage Load Switch

Indoor High Voltage Load Switch

Introduction: FN18-12 Indoor High Voltage Load Switch [Vacuum Circuit Breaker] 
FN18-12 Series Indoor High Voltage Load Switch has such advantages as: advanced design, convenient operation, compact structure, small volume, light weight, rapid opening and closing speed, high reliability and so on. It is applied to AC 50Hz 12kV rated voltage 630 rated current three-phase power distribution systems. It is especially suited for the ring net power supply of urban network construction and renovation project, high-rise building and public facilities. It is the ideal product for electrical substation and transformer protection.
Working & Environmental Conditions - Indoor High Voltage Load Switch
1. Environmental temperature: maximum +40°C, minimum -25°C
2. Altitude: 1000m
3. Relative humidity: daily average value smaller than 95%, monthly average value smaller than 90%
4. The surrounding air should be in the absence of the obvious pollution of corrosion, flammable gas
5. No regular dramatic shake
Model Meaning
Technical Parameters - High Voltage Load Switch [ Vacuum Circuit Breaker ]
Order Name Unit FN18-12D/630 FN18-12DR/100-31.5
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 Rated current A 630 100
4 Lightening impact voltage tolerance kV Towards the ground and alternated 42, isolation fracture48
1min work frequency voltage tolerance Towards the ground and alternated 75, isolation fracture 85
5 Phase distance Mm 170
6 Rated dynamic stable current kA 50
7 Rated thermal stable current kA/S 20/2
8 Rated cable charging current A 10
9 Rated transfer current 1600
10 Breaking unload transformer energy kva 1250
11 Rated short circuit breaking current (fuse value) KA 31.5-50
12 Rated fuse closing current (peak value) 50
13 Rated active load breaking current 630
14 Ground switch rated thermal stable current kA/S 16/2
15 Rated active load current breaking times (Times) 100
16 Mechanical life span 2000
  Contour & Installation Dimensions - High Voltage Load Switch

Back