High Voltage Electric Components - High Voltage Load Switch [Vacuum Circuit Breaker]

Indoor High Voltage Load Switch

Indoor High Voltage Load Switch and Fuse Combined Electrical Appliance

Introduction: FN7-12 Indoor High Voltage Load Switch [Electrical Switch]
FN7-12DR AC High Voltage Load Switch is a new type of gas-production indoor high voltage load switch which applies to three-phase AC 50 Hz 10kV rated voltage power system for opening the load current and closing the short circuit.
Working & Environmental Conditions - FN7-12 Indoor High Voltage Load Switch [Vacuum Circuit Breaker]
1. Environmental temperature: maximum +40°C, minimum -25°C
2. Altitude: 1000m
3. Relative humidity: daily average value smaller than 95%, monthly average value smaller than 90%
4. The surrounding air should be in the absence of the obvious pollution of corrosion, flammable gas
5. No regular dramatic shake
Model Meaning - FN7-12 High Voltage Load Switch [Vacuum Circuit Breaker]

Main Specifications - High Voltage Load Switch [Electrical Switch]
Table One
Category Complete model DS ground switch at the wire access end DX ground switch at the wire access end L interlock device R fuse RA collision fuse F motor Switch opening device
  without button release MFN7-12
MFN7-12D SL
MFN7-12D XL
MFN7-12R
MFN7-12D SLR
MFN7-12D XLR
With collision button release MFN7-12RAF
MFN7-12D SL RAF
MFN7-12D XL RAF  
Note: “一”without, “△”with, newly developed: PN7C-10400.630 side installed and frontage operated
Rated Parameters - Table Two
Rated voltage (KV) Maximum voltage(KA) Rated current(A) 1min work frequency voltage tolerance(KA) 4S thermal stable current (RMS)(KA) Dynamic stable current(KA) Short circuit closing current(KA) Rated breaking current(A) Rated transfer current(A)
12 12 400 42/48 12.5 31.5 31.5 400 1000
630 42/48 20 50 50 630 1000
Rated parameter of the fuse  - Table Three
Model Rated voltage(KV) Rated current(A) Rated current of the fuse(A)
SDLA﹡J 12 40 63, 10, 16, 20, 25, 31.5, 40
SFLA﹡J 12 100 50, 63, 71, 80, 100
SKLA﹡J 12 125 125
  Contour & Installation Dimensions - High Voltage Load Switch Back