Introduction: FN5-12 Indoor High Voltage Load Switch [Vacuum Circuit Breaker]
FN5-12R(L)Indoor High Voltage Load Switch and Fuse Combined Electrical Appliance is designed and developed by our company which has assimilated foreign advanced technology with our domestic power supply requirements. This product has passed comprehensive model test and long term trial operation examination. Its performance has reached IEC420"AC High Voltage Load Switch-Fuse Combined Electrical Appliance" (1990 version)and GB3804"3-63kV AC High Voltage Load Switch" . Its technical parameters have reached the level of similar products. It has small volume and light weight and can be used in ring net box as well as electrical substation. It is widely applied to 12kV circuit power distribution and has effectively avoided operating in lack of phase.
The research of the product has successfully filled the domestic blank and realized switch, isolation and grounding these three working position.
Terms of use: FN5-12 Indoor High Voltage Load Switch [Vacuum Circuit Breaker]
1. Environmental temperature: maximum +40°C, minimum -25°C
2. Altitude: 1000m
3. Relative humidity: daily average value smaller than 95%, monthly average value smaller than 90% (+25°C)
4. The surrounding air should be in the absence of the obvious pollution of corrosion, flammable gas
5. No regular dramatic shake
Technical Parameters - Indoor High Voltage Load Switch
Table One - Load switch-fuse combined electrical appliance
Name Unit Data
Rated voltage KV 12
Rated frequency Hz 50
Rated current A 100
Rated short circuit breaking current kA 50
1min work frequency voltage tolerance (RMS)towards the ground, alternated/ isolated fracture kA 42/48
Lightening impact voltage (peak value) towards the ground, alternated/ isolated fracture KV 75/85
Collision energy output of Fuse kg ≈5
    Table Two - Load switch of the combined electrical appliance
Name Unit Data
Rated voltage KV 12
Rated frequency Hz 50
Rated current A 630
Rated active load current A 630
5% rated active load breaking current A 31.5
Rated capacitor breaking current A 10
Rated sensor breaking current A 40
Rated transfer current kA 1.3
Rated short term current tolerance kA 20
Rated peak value current tolerance kV 50
Mechanical life span Times 2000
  Contour & Installation Dimensions - High Voltage Load Switch Back