High Voltage Electric Components - High Voltage Vacuum Load Switch

High Voltage Vacuum Load Switch

Outdoor Pole Mounted High Voltage Vacuum Load Switch

Introduction - High Voltage Vacuum Load Switch [Vacuum Circuit Breaker]
FZW32-12/T630-20 Outdoor Pole Mounted High Voltage Vacuum Load Switch is a new generation of high voltage electrical equipments which has integrated domestic and foreign technology. It has experienced strict model test and long term trial operation. All its performances have reached GB3804 and IC standards.
It is mainly designed for urban and rural network construction and renovation and adopts the three-phase 12 KV rated voltage 50 Hz power supply system. Its chassis adopts stainless steel material and hot galvanized carbon steel with anti-ultraviolet coating layer which guarantees the normal operation outside. Its parts adopt stainless material to assure the endurance of the load switch, stability and water-proof, salt-proof performances.
It has a small volume, light weight, pleasing appearance, convenient operation, high parameter, strong opening ability, long life span, frequent operation, few maintenance and obvious fracture, etc. such outstanding features. It can be operated by manual single rod or electrical, remote control
Working & Environmental Conditions - High Voltage Vacuum Load Switch [Vacuum Circuit Breaker]
1. Surrounding air temperature: +40°C~-30°C (below -45°C can be provide for special requirement)
2. Altitude lower than 1000m, 2000m, 3000m
3. Wind pressure smaller than 700Pa(equals to wind speed of 34m/s)
4. Filthy rank lower than IV
5. No regular dramatic shake and earthquake intensity smaller than 8 degree.

Model Meaning
Parameters - High Voltage Vacuum Load Switch [Vacuum Circuit Breaker]     Table One
Order Name Unit Parameter
1 Rated voltage KV 12
2 Rated frequency HZ 50
3 Rated current A 630
4 Rated load active breaking current A 630
5 Rated closed loop breaking current A 630
6 5%rated active load breaking current A 31.5
7 Rated cable charge breaking current A 10
8 Imin work frequency voltage tolerance vacuum fracture/alternated towards the ground/isolated fracture KV 42/48
9 Lightening impact current tolerance: alternated /towards the ground/isolated fracture KV 75/85
10 Rated short term current tolerance (thermal stable) KA 20
11 Rated short circuit duration time S 4
12 Rated peak value current tolerance (dynamic stable) KA 50
13 Rated short circuit closing current KA 50
14 Mechanical life span Times 10000
15 Vacuum arc chamber contact allowed accumulated attrition thickness Mm 0.5
16 Manual operation torque Nm ≤200
17 Rated unload transformer breaking capacity Kva 1600
18 Rated breaking capacitor group current A 100
19 Weight kg 100
Mechanical Features Parameters - High Voltage Vacuum Load Switch [Vacuum Circuit Breaker] 
Table Two
Order Name Unit Parameter
1 Contact openness size Mm 5±1
2 Average Switch opening speed M/s 1.1±0.2
3 Different periods of three-phase Switch opening Ms ≤5
4 Different periods of three-phase Switch closing Ms ≤2
5 Circuit resistance of each phase circuit µΩ ≤400
6 Inter and relative distances of charged objects Mm >200
Contour & Installation Dimensions - Vacuum Circuit Breaker Back