Introduction - High Voltage Vacuum Load Switch [Vacuum Circuit Breaker]
FZW□-12G/T□, 630 Outdoor Pole Mounted High Voltage Load Switch adopts SF6 gas as the arc chamber and insulation media. It is mainly used in the AC 50 Hz 12 kV rated voltage transmission circuit for opening and closing the load current as well as the partition transformer, unload current and capacitor group current. It also can be used as partition switch. This load switch is configured with spring operation mechanism which can operate manually or electrically. It is applied to frequently used places.
Working & Environmental Conditions - High Voltage Vacuum Load Switch
1. Surrounding air temperature: +40°C~-30°C (below -45°C can be provide for special requirement)
2. Altitude lower than 1000m, 2000m, 3000m
3. Wind pressure smaller than 700Pa(equals to wind speed of 34m/s)
4. Filthy rank lower than IV
5. No regular dramatic shake and earthquake intensity smaller than 8 degree.

Model Meaning
Parameters - High Voltage Vacuum Load Switch [ Vacuum Circuit Breaker]
Table One
Order Name Unit Parameter
1 Rated voltage KV 40.5
2 Rated frequency HZ 50
3 Rated current A 1250
4 Rated load active breaking current A 1250
5 Rated closed loop breaking current A 1250
6 5%rated active load breaking current A 62.5
7 Rated cable charge breaking current A 25
8 Imin work frequency voltage tolerance vacuum fracture/alternated towards the ground/isolated fracture KV 95/110
9 Lightening impact current tolerance: alternated /towards the ground/isolated fracture KV 185/215
10 Rated short term current tolerance (thermal stable) KA 25
11 Rated short circuit duration time S 4
12 Rated peak value current tolerance (dynamic stable) KA 63
13 Rated short circuit closing current KA 63
14 Mechanical life span Times 10000
15 Vacuum arc chamber contact allowed accumulated attrition thickness Mm 0.6
16 Manual operation torque Nm ≤300
17 Weight kg 500
Mechanical Features Parameters - High Voltage Vacuum Load Switch
Table Two
Order Name Unit Parameter
1 Contact openness size Mm 13±1
2 Average Switch opening speed M/s 1.4±0.2
3 Different periods of three-phase Switch opening Ms ≤5
4 Different periods of three-phase Switch closing Ms ≤2
5 Inter and relative distances of charged objects Mm ≤420
6 Auxiliary circuit resistance µΩ 400≥R≤1000
Isolate switch assembly & adjustment technical parameters                     Table Three
Order Name Unit Parameter
1 Isolate knife pressure N 500±50
2 Distance between the final end of the contact knife and the static contact small fracture/large fracture Mm ≥180/420
3 Resistance of the access and outlet terminals µΩ ≤150
Contour & Installation Dimensions - High Voltage Vacuum Load Switch Back