Outdoor Pole Mounted High Voltage Vacuum Load Switch
Introduction - High Voltage Vacuum Load SwitchFZW□-12G/T□, 630 Outdoor Pole Mounted High Voltage Load Switch adopts SF6 gas as the arc chamber and insulation media. It is mainly used in the AC 50 Hz 12 kV rated voltage transmission circuit for opening and closing the load current as well as the partition transformer, unload current and capacitor group current. It also can be used as partition switch. This load switch is configured with spring operation mechanism which can operate manually or electrically. It is applied to frequently used places.
Working & Environmental Conditions - High Voltage Vacuum Load Switch
1. Surrounding air temperature: +40°C~-30°C (below -45°C can be provide for special requirement)
2. Altitude lower than 1000m, 2000m, 3000m
3. Wind pressure smaller than 700Pa (equals to wind speed of 34m/s)
4. Filthy rank lower than IV
5. No regular dramatic shake and earthquake intensity smaller than 8 degree.
Model Meaning
Technical Parameters - High Voltage Vacuum Load Switch| Order | Name | Unit | Parameter | ||
| 1 | Rated voltage | KV | 12 | ||
| 2 | Rated insulation level | Imin work frequency voltage tolerance | Dry test | 42 | |
| wet test | 34 | ||||
| Lightening impact current tolerance (peak value | 75 | ||||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Rated current | A | 400, 630 | ||
| 5 | Rated closed loop breaking current | A | |||
| 6 | Rated short term current tolerance | KV | 20 | ||
| 7 | Rated peak value current tolerance (peak value) | KV | 50 | ||
| 8 | Rated short circuit closing current (peak value) | KV | 50 | ||
| 9 | Rated short circuit duration time | S | 4 | ||
| 10 | Rated unload transformer breaking capacity | KVA | 1250 | ||
| 11 | Mechanical life span | Times | 10000 | ||
| 12 | Rated operation cycle | Close-open | |||
| 13 | Protection CT | Ratio | A | ( )/5 | |
| Capacity | VA | 15 | |||
| 14 | Weight | Kg | 110 | ||
1 Switch opening release button positioning - 2 Lock board - 3 Crank link rod - 4 Bounce button - 5 Reset spring - 6 Switch closing spring 7 Switch closing rod mechanism - 8 Trailer - 9 Interlock rod - 10 Switch opening spring - 11 shaft
1 Insulate cover tube - 2 Self-sealed gate - 3 spring mechanism - 4 isolate operation handle - 5 ground bolt 6 Switch closing handle bar - 7 Isolate fracture
1 Switch closing state sign 2 Switch closing handle (Switch closing position)1 Switch opening state sign 2 Switch closing handle (Switch opening position)
Back 