Outdoor Pole Mounted High Voltage SF6 Automatic Partition Slotter
Introduction - Automatic Partition Slotter [Electrical Switch]FDL4-12/400Outdoor Pole Mounted High Voltage SF6 Automatic Partition Slotter adopts SF6 gas as the arc chamber and insulation media.
It is mainly used in the three-phase AC 50 Hz 12 kV rated voltage transmission circuit as the control and protection equipment. It can be used with recloser, circuit breaker and fuse. If the load side circuit or the equipment breaks down, the failure current reached or exceed the rated starting current setting value, the partition slotter would count the break actions of the reserved protection equipment. Once the counted number reaches the setting value, the partition slotter will automatically open the switch and lock it.
The partition slotter has lock state memory function and can automatically skip the switch with the connection to single phase generatrix without other auxiliary power supply. It can carry out opening and closing remote control on the spot as well as connected to RS485 interface which achieves three remotes.
Working & Environmental Conditions - Automatic Partition Slotter
1. The battery adopts electronic PT, AC220V, CT charge which is safe and reliable.
2. Installed with rs 485, rs232 two communications interfaces and several communication protocol
3. “Four remote” functions: remote control, remote adjustment, remote communication and remote measure.
4. The devices are installed a remote control switch at the distance of 30 meters.
5. Provide the protection of management functions. The users can easily Model Meaning
Technical Parameters - Automatic Partition SlotterTable One
| Order | Name | Unit | Parameter | |||
| 1 | Rated voltage | KV | 12 | |||
| 2 | KV(peak value) | 75 | ||||
| Imin work frequency voltage tolerance | Dry test | KV | 30 | |||
| Wet test | (RMS) | 42 | ||||
| 3 | Rated current | A | 200 | 400 | ||
| 4 | Rated load breaking current | A | 200 | 400 | ||
| 5 | Rated short circuit closing current | KV (peak value) | 20 | 25 | ||
| 6 | Rated dynamic stable current | KV(peak value) | 20 | 25 | ||
| 7 | Rated thermal stable current | KA | 8 | 10 | ||
| 8 | Rated thermal stable current transmission time | S | 4 | 4 | ||
| 9 | Rated working barometric pressure (20°C meter pressure) | MPa | 0.18 | |||
| 10 | Minimum working barometric pressure (20°C meter pressure) | MPa | 0.162 | |||
| 11 | SF6 water content | Ppm | ≤150 | |||
| 12 | Annual leakage rate | % | ≤1 | |||
| 13 | Mechanical life span | Times | 3000 | |||
| 14 | Protection CT | Ratio | A | ( )/5 | ||
| Capacity | VA | 15 | ||||
| 15 | Weight | Kg | 140 | |||
Table Two
| Order | Name | Unit | Parameter |
| 1 | Breakdown Switch opening time | Second | ≤0.4 |
| 2 | Rated memory times | Times | 1~4(adjustable) |
| 3 | Rated memory time | Second | 0~50(adjustable) |
| 4 | Rated current of start setting | A | 20~4000(adjustable) |
| 5 | Single ground delayed time | Second | 10~7200(adjustable) |
| 6 | Rated voltage of the Switch opening release button | V | Dc 24V Ac 220V |
| 7 | Environmental temperature | °C | -40°C~85°C |
| 8 | Simulate measure error | ≤29% |
1 Switch opening release button positioning - 2 Lock board - 3 Crank link rod - 4 Bounce button - 5 Reset spring - 6 Switch closing spring 7 Switch closing rod mechanism - 8 trailer - 9 Interlock rod - 10 Switch opening spring - 11 Shaft
Left 1 Insulate cover tube - 2 Manometer - 3 Self-sealed gate - 4 Spring mechanism - 5 Switch opening handle bar 6 Switch closing handle bar - 7 Controller
Right 1 Partition slotter - 2 angle steel (self-prepared) - 3 ground row (self-prepared) - 4 Screw and nut (self-prepared)