Automatic Partition Slotter

Outdoor Pole Mounted High Voltage SF6 Automatic Partition Slotter

Introduction - Automatic Partition Slotter [Electrical Switch]
FDL4-12/400Outdoor Pole Mounted High Voltage SF6 Automatic Partition Slotter adopts SF6 gas as the arc chamber and insulation media.
It is mainly used in the three-phase AC 50 Hz 12 kV rated voltage transmission circuit as the control and protection equipment. It can be used with recloser, circuit breaker and fuse. If the load side circuit or the equipment breaks down, the failure current reached or exceed the rated starting current setting value, the partition slotter would count the break actions of the reserved protection equipment. Once the counted number reaches the setting value, the partition slotter will automatically open the switch and lock it.
The partition slotter has lock state memory function and can automatically skip the switch with the connection to single phase generatrix without other auxiliary power supply. It can carry out opening and closing remote control on the spot as well as connected to RS485 interface which achieves three remotes.
Working & Environmental Conditions - Automatic Partition Slotter
1. The battery adopts electronic PT, AC220V, CT charge which is safe and reliable.
2. Installed with rs 485, rs232 two communications interfaces and several communication protocol
3. “Four remote” functions: remote control, remote adjustment, remote communication and remote measure.
4. The devices are installed a remote control switch at the distance of 30 meters.
5. Provide the protection of management functions. The users can easily

Model Meaning
Technical Parameters - Automatic Partition Slotter
Table One
Order Name Unit Parameter
1 Rated voltage KV 12
2 KV(peak value) 75
Imin work frequency voltage tolerance Dry test KV 30
Wet test (RMS) 42
3 Rated current A 200 400
4 Rated load breaking current A 200 400
5 Rated short circuit closing current KV (peak value) 20 25
6 Rated dynamic stable current KV(peak value) 20 25
7 Rated thermal stable current KA 8 10
8 Rated thermal stable current transmission time S 4 4
9 Rated working barometric pressure (20°C meter pressure) MPa 0.18
10 Minimum working barometric pressure (20°C meter pressure) MPa 0.162
11 SF6 water content Ppm ≤150
12 Annual leakage rate % ≤1
13 Mechanical life span Times 3000
14 Protection CT Ratio A ( )/5
Capacity VA 15
15 Weight Kg 140

Table Two
Order Name Unit Parameter
1 Breakdown Switch opening time Second ≤0.4
2 Rated memory times Times 1~4(adjustable)
3 Rated memory time Second 0~50(adjustable)
4 Rated current of start setting A 20~4000(adjustable)
5 Single ground delayed time Second 10~7200(adjustable)
6 Rated voltage of the Switch opening release button V Dc 24V Ac 220V
7 Environmental temperature °C -40°C~85°C
8 Simulate measure error   ≤29%
Contour & Installation Dimensions - Atomatic Partition Slotter 1 Switch opening release button positioning - 2 Lock board - 3 Crank link rod - 4 Bounce button - 5 Reset spring - 6 Switch closing spring
7 Switch closing rod mechanism - 8 trailer - 9 Interlock rod - 10 Switch opening spring - 11 ShaftLeft 1 Insulate cover tube - 2 Manometer - 3 Self-sealed gate - 4 Spring mechanism - 5 Switch opening handle bar
6 Switch closing handle bar - 7 Controller
Right 1 Partition slotter - 2 angle steel (self-prepared) - 3 ground row (self-prepared) - 4 Screw and nut (self-prepared)