High Voltage Electric Components - High Voltage Atomatic Recloser [Vacuum Circuit Breaker]

High Voltage Automatic Recloser

Outdoor Pole Mounted High Voltage Automatic Recloser

Introduction - High Voltage Automatic Recloser  
CHZ(Ⅱ)-12/630-20 Outdoor Pole Mounted High Voltage Automatic Recloser (hereinafter refers to the “recloser”) is a three-phase AC 50 Hz outdoorHigh Voltage Electric Componentsequipment. It is mainly used as 10kV side wire outlet and circuit protection switch in urban and rural substations. It can automatically monitor the operations of power transmission circuit and accurately judge temporary failure and permanent failure. It can fix more than 95% temporary failure. The recloser can open and close the switch according to the preset opening and reclosing sequence in the AC circuit as well as automatically reset or lock it. If used with the partition slotter , the system can maximally reduce the power failure range and time without other control system. It is also configured standard RS232, 485 communication interface, four remote control functions which provide powerful support for the full automation of power system.
Functional Features - High Voltage Automatic Recloser
1. Computer control device is configured with a group of 20 batteries. The battery capacity can work for 50-hour.
2. The battery adopts electronic PT, AC220V, CT charge which is safe and reliable.
3. The devices are installed a remote control switch at the distance of 30 meters. The on-site operators need not to climb poles.
4. Provide the protection of management functions. The users can easily modify current skip within a flexible setting value.

Model Meaning
Technical Parameters - High Voltage Automatic Recloser
Table One
Order Name Unit Parameter
1 Rated voltage KV 12
2 Rated current A 630/1250
3 Rated frequency Hz 50
4 Imin work frequency voltage tolerance Dry test KV 42/49
Wet test 30
5 Lightening impact current tolerance (peak value) alternated, towards the ground/fracture KV 75/85
6 Rated short circuit breaking current KA 20
7 Rated short circuit closing current (peak value) KA 50
8 Rated peak value current tolerance KA 50
9 4S short term current tolerance KA 20
10 Rated operation cycle   Open-0.3s-slose-open-180s-close-open
11 Rated times of short circuit breaking current Times 30
12 Mechanical life span Times 50000
13 Secondary circuit I min work frequency voltage tolerance KV 2
14 Protection CT Ratio A ( )/5
Capacity VA 15
15 Weight Kg 180
16 Reclose interval Second 0~50 (adjustable)
17 Setting times of reclosing the switch Times 1~4 (adjustable)
18 Start current setting of the overload current A 20~4000 (adjustable)
19 Delayed time of setting the overload current Second 0~50 (adjustable)
20 Start setting current of immediate break A 20~4000 (adjustable)
21 Rated energy storage voltage V Dc 24V Ac 220V
22 Rated voltage of opening/closing the switch release button V Dc 24V Ac 220V
23 Simulate measure error ≤29%
Table Two
Order Name Unit Parameter
1 Contact openness size Mm 11±1
2 Contact excess travel Mm 3+1.0-0.3
3 Average Switch closing speed M/s 0.65±0.15
4 Average Switch opening speed M/s 1.1±0.2
5 Differences of three-phase Switch opening at the same period Ms ≤2
6 Switch closing and bouncing time Ms ≤2
7 Switch closing time Ms ≤60
8 Switch opening time Ms ≤70
9 DC resistance of each phase circuit µΩ ≤200
10 Dynamic, static contacts allowed accumulated attrition thickness Mm 3
Contour & Installation Dimensions - High Voltage Automatic Recloser

Picture I Contour & Installation Dimensions Diagram of the Circuit BreakerPicture II Structure, Contour and Installation Dimensions Diagram of the Combined Circuit Breaker
1 contact blade
2 contact knives
3 Insulate pull bar
4 the support
5 handle bar of the isolate switch
6 shaft
7 support of the isolate switch
8 circuit breaker