Outdoor High Voltage PM Vacuum Circuit Breaker (Recloser, Partition Slotter)
Introduction - High Voltage PM Vacuum Circuit Breaker1. ZW32-12/M630-20 Outdoor High Voltage PM Vacuum Circuit Breaker (Recloser, Partition Slotter) is an outdoor high voltage power distribution device of three-phase 50 Hz 12 kV rated voltage 630A~1250A rated current 16KA~20KA rated short circuit current.
2. It is mainly used in opening and closing the overload current, load current as well as short circuit current of the power system. It is applied to protect and control the power distribution system of industrial mining enterprises as well as rural network and frequently operated places.
3. The product has kept all the reasonable structure and good performance of the former ZW32, which improved the overall mechanical life span including the arc chamber. It can be used for sixty thousand times and thirty times free of maintenance.
4. By expansion, it can be conveniently assembled into reclose and partition slotter which can distinguish temporary failure from permanent failure. Meanwhile, it can realize various network compositions, protection and operation functions in accordance with the customers by making use t of the powerful controlling function of the permanent magnetic actuator.
Functional Features - High Voltage PM Vacuum Circuit Breaker
1. Computer control device is configured with a group of 20 batteries. The battery capacity can work for 50-hour.
2. The battery adopts electronic PT, AC220V, CT charge which is safe and reliable.
3. The devices are installed a remote control switch at the distance of 30 meters. The on-site operators need not to climb poles.
4. Provide the protection of management functions. The users can easily modify current skip within a flexible setting value.
Model Meaning
Main Parameters - High Voltage PM Vacuum Circuit BreakerTable One
| Order | Name | Unit | Parameter | ||
| 1 | Rated voltage | KV | 12 | ||
| 2 | Rated current | A | 630/1250 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Imin work frequency voltage tolerance | Dry test | KV | 42/49 | |
| Wet test | 30 | ||||
| 5 | Lightening impact current tolerance (peak value) alternated, towards the ground/fracture | KV | 75/85 | ||
| 6 | Rated short circuit breaking current | KA | 20 | ||
| 7 | Rated short circuit closing current (peak value) | KA | 50 | ||
| 8 | Rated peak value current tolerance | KA | 50 | ||
| 9 | 4S short term current tolerance | KA | 20 | ||
| 10 | Rated operation cycle | open-0.3s-slose-open-180s-close-open |
|||
| 11 | Rated times short circuit breaking current | Times | 30 | ||
| 12 | Mechanical life span | Times | 50000 | ||
| 13 | Secondary circuit I min work frequency voltage tolerance | KV | 2 | ||
| 14 | Protection CT | Ratio | A | ( )/5 | |
| Capacity | VA | 15 | |||
| 15 | Weight | Kg | 100 | ||
| 16 | Reclose interval | Second | 0~50(adjustable) | ||
| 17 | Setting times of reclosing the switch | Times | 1~4 (adjustable) | ||
| 18 | Start current setting of the overload current | A | 20~4000(adjustable) | ||
| 19 | Delayed time of setting the overload current | Times | 0~50 (adjustable) | ||
| 20 | Start setting current of immediate break | A | 20~4000(adjustable) | ||
| 21 | Rated energy storage voltage | V | Dc 24V Ac 220V | ||
| 22 | Rated voltage of opening/closing the switch release button | V | Dc 24V Ac 220V | ||
| 23 | Simulate measure error | ≤29% | |||
Table Two
| Order | Name | Unit | Parameter |
| 1 | Contact openness size | Mm | 11±1 |
| 2 | Contact excess travel | Mm | 3+1.0-0.3 |
| 3 | Average Switch closing speed | M/s | 0.65±0.15 |
| 4 | Average Switch opening speed | M/s | 1.1±0.2 |
| 5 | Differences of three-phase Switch opening at the same period | Ms | ≤2 |
| 6 | Switch closing and bouncing time | Ms | ≤2 |
| 7 | Switch closing time | Ms | ≤60 |
| 8 | Switch opening time | Ms | ≤70 |
| 9 | DC resistance of each phase circuit | µΩ | ≤200 |
| 10 | Dynamic, static contacts allowed accumulated attrition thickness | Mm | 3 |
Contour & Installation Dimensions Diagram of MZW32-12G/M630-20 (with isolate switch)
Contour & Installation Dimensions Diagram of MCHZ 32-12G
1 Isolate knife
2 Insulate railings
3 Insulator
4 Static contact
5 isolate switch support
6 handle bar of the isolate switch
7 Isolate switch support
8 Interlock rod