High Voltage Electric Components - High Voltage Vacuum Circuit Breaker

Outdoor High Voltage Vacuum Circuit Breaker

Outdoor High Voltage Vacuum Circuit Breaker


Introduction - High Voltage Vacuum Circuit Breaker
ZW6-12/T630-20 Outdoor High Voltage Vacuum Circuit Breaker (hereinafter refers to circuit breaker) applies to AC 50Hz 10~12KV voltage three-phase power system for opening and closing the load current. The product has protection function for overload and short circuit as well as can automatically close the switch. Users can configure protector for delaying surging current and the isolate switch with avoiding the lightening function (that is the circuit breaker combined with the isolate switch. Hereinafter refers to “combined circuit breaker”), etc.
Working & Environmental Conditions - High Voltage Vacuum Circuit Breaker
1. Surrounding air temperature: -40°C~+55°C, daily temperature difference: 25°C
2. Altitude: less than 2000m
3. Wind pressure: smaller than 700Pa (equals to wind speed 35m/s)
4. No regular dramatic shake; Earthquake intensity is smaller than 8 degree
5. No strong corrosion gas or medium (such as acids, alkali and heavy smoke )
6. Anti-filthy rank: Ⅳ
Model Meaning
Main Technical Parameters - Vacuum Circuit Breaker
Table One
Order Name Unit Parameter
1 Rated voltage KV 12
2 Rated current A 630
3 Rated frequency Hz 50
4 Imin work frequency voltage tolerance Dry test KV 42/49
Wet test 34
5 Lightening impact current tolerance (peak value) alternated, towards the ground/fracture KV 75/85
6 Rated short circuit breaking current KA 20
7 Rated short circuit closing current (peak value) KA 50
8 Rated peak value current tolerance KA 50
9 4S short term current tolerance KA 20
10 Rated operation cycle Open-0.3s-close-open-180s-close-open
11 Rated times short circuit breaking current Times 30
12 Mechanical life span Times 30000
13 Secondary circuit I min work frequency voltage tolerance KV 2
14 Protection CT Ratio A ( )/5
Capacity VA 15
15 Weight Kg 180
Table Two
Order Name Unit Parameters
1 Contact openness size Mm 11±1
2 Contact excess travel Mm 3+1.0-0.3
3 Average Switch closing speed M/s 0.65±0.15
4 Average Switch opening speed M/s 1.1±0.2
5 Differences of three-phase Switch opening at the same period Ms ≤2
6 Switch closing and bouncing time Ms ≤2
7 Switch closing time Ms ≤60
8 Switch opening time Ms ≤70
9 DC resistance of each phase circuit µΩ ≤200
10 Dynamic, static contacts allowed accumulated attrition thickness Mm 3
Contour & Installation Dimensions

Picture 1 Contour & Installation Dimensions Diagram of ZW6-12/T Picture 2 Contour & Installation Dimensions Diagram of ZW6-12G/T