Outdoor High Voltage Vacuum Circuit Breaker
Introduction - High Voltage Vacuum Circuit Breaker
ZW6-12/T630-20 Outdoor High Voltage Vacuum Circuit Breaker (hereinafter refers to circuit breaker) applies to AC 50Hz 10~12KV voltage three-phase power system for opening and closing the load current. The product has protection function for overload and short circuit as well as can automatically close the switch. Users can configure protector for delaying surging current and the isolate switch with avoiding the lightening function (that is the circuit breaker combined with the isolate switch. Hereinafter refers to “combined circuit breaker”), etc.
Working & Environmental Conditions - High Voltage Vacuum Circuit Breaker
1. Surrounding air temperature: -40°C~+55°C, daily temperature difference: 25°C
2. Altitude: less than 2000m
3. Wind pressure: smaller than 700Pa (equals to wind speed 35m/s)
4. No regular dramatic shake; Earthquake intensity is smaller than 8 degree
5. No strong corrosion gas or medium (such as acids, alkali and heavy smoke )
6. Anti-filthy rank: Ⅳ
Model Meaning
Main Technical Parameters - Vacuum Circuit BreakerTable One
| Order | Name | Unit | Parameter | ||
| 1 | Rated voltage | KV | 12 | ||
| 2 | Rated current | A | 630 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Imin work frequency voltage tolerance | Dry test | KV | 42/49 | |
| Wet test | 34 | ||||
| 5 | Lightening impact current tolerance (peak value) alternated, towards the ground/fracture | KV | 75/85 | ||
| 6 | Rated short circuit breaking current | KA | 20 | ||
| 7 | Rated short circuit closing current (peak value) | KA | 50 | ||
| 8 | Rated peak value current tolerance | KA | 50 | ||
| 9 | 4S short term current tolerance | KA | 20 | ||
| 10 | Rated operation cycle | Open-0.3s-close-open-180s-close-open | |||
| 11 | Rated times short circuit breaking current | Times | 30 | ||
| 12 | Mechanical life span | Times | 30000 | ||
| 13 | Secondary circuit I min work frequency voltage tolerance | KV | 2 | ||
| 14 | Protection CT | Ratio | A | ( )/5 | |
| Capacity | VA | 15 | |||
| 15 | Weight | Kg | 180 | ||
| Order | Name | Unit | Parameters |
| 1 | Contact openness size | Mm | 11±1 |
| 2 | Contact excess travel | Mm | 3+1.0-0.3 |
| 3 | Average Switch closing speed | M/s | 0.65±0.15 |
| 4 | Average Switch opening speed | M/s | 1.1±0.2 |
| 5 | Differences of three-phase Switch opening at the same period | Ms | ≤2 |
| 6 | Switch closing and bouncing time | Ms | ≤2 |
| 7 | Switch closing time | Ms | ≤60 |
| 8 | Switch opening time | Ms | ≤70 |
| 9 | DC resistance of each phase circuit | µΩ | ≤200 |
| 10 | Dynamic, static contacts allowed accumulated attrition thickness | Mm | 3 |
Picture 1 Contour & Installation Dimensions Diagram of ZW6-12/T
Picture 2 Contour & Installation Dimensions Diagram of ZW6-12G/T