High Voltage Electric Components - High Voltage Vacuum Circuit Breaker

Outdoor High Voltage Vacuum Circuit Breaker

Outdoor High Voltage Vacuum Circuit Breaker

Introduction - High Voltage Vacuum Circuit Breaker
ZW32 -12/T630-20 Outdoor Vacuum Circuit Breaker applies to three-phase AC 50Hz 12kV rated voltage and below outdoor power transformation and distribution system. It is widely used in rural network construction and renovation, industrial mining enterprises power distribution system as well as other public facilities. It can be used for the power distribution and control of ring net power supply unit and terminal devices as well as protecting the electrical devices. This product has such features as: small volume, light weight (lighter than 100Kg), long life span, reliable, safe, convenient operation, maintenance and installation.
Working & Environmental Conditions - High Voltage Vacuum Circuit Breaker
1. Surrounding air temperature: -40°C~+55°C, daily temperature difference: 25°C
2. Altitude: lower than 2000m
3. Wind pressure: smaller than 700Pa (equals to wind speed 35m/s)
4. No regular dramatic shake, earthquake intensity should smaller than 8 degree.
5. No strong corrosion gas or medium (such as acids, alkali and heavy smoke )
6. Anti-filthy rank: Ⅳ
Model Meaning
Technical Parameters - High Voltage Vacuum Circuit Breaker
Table I
Order Name Unit Parameter
1 Rated voltage KV 12
2 Rated current A 630/1250
3 Rated frequency Hz 50
4 Imin work frequency voltage tolerance Dry test KV 42/49
Wet test 30
5 Lightening impact current tolerance (peak value) alternated, towards the ground/fracture KV 75/85
6 Rated short circuit breaking current KA 20
7 Rated short circuit closing current (peak value) KA 50
8 Rated peak value current tolerance KA 50
9 4S short term current tolerance KA 20
10 Rated operation cycle   Open-0.3s-slose-open-180s-close-open
11 Rated times of short circuit breaking current Times 30
12 Mechanical life span Times 50000
13 Secondary circuit I min work frequency voltage tolerance KV 2
14 Protection CT Ratio A ( )/5
Capacity VA 15
15 Weight Kg 100

Table II
Order Name Unit Parameter
1 Contact openness size Mm 11±1
2 Contact excess travel Mm 3+1.0-0.3
3 Average Switch closing speed M/s 0.65±0.15
4 Average Switch opening speed M/s 1.1±0.2
5 Differences of three-phase Switch opening at the same period Ms ≤2
6 Switch closing and bouncing time Ms ≤2
7 Switch closing time Ms ≤60
8 Switch opening time Ms ≤70
9 DC resistance of each phase circuit µΩ ≤200
10 Dynamic, static contacts allowed accumulated attrition thickness Mm 3
Contour & Installation Dimensions
Picture I ZW32-12/T630-20 Contour and Installation Dimensions
1 Insulate cover cylinder
2 Vacuum arc chamber (inside the cover tube)
3 Hoist ring
4 Switch opening and closing handle
5 Energy storage handle
6 The box
7 PM (inside the box)
8 Switch opening and closing instruction
9 Aviation plug
10 Electric sensor

Picture II ZW32-12G/T630-20 (with isolate switch) Contour and Installation Dimensions
1 Isolate knife
2 Insulate pull bar
3 Insulator
4 Static contact
5 isolate switch support
6 Isolate switch operation handle
7 Isolate switch support
8 Interlock bar
Back