Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker
Introduction - High Voltage Vacuum Circuit BreakerZW8-12/T630-20 Outdoor Pole Mounted High Voltage Vacuum Circuit Breaker is a three-phase AC 50Hz 12kV rated voltage outdoor power distribution device. It is mainly used in opening and closing the load current, overload current and short circuit current of the power system. It suits for the substation and industrial mining enterprises power distribution system for protection and control as well as rural network and other frequently operated places. If combined with the controller, it can meet power distribution automation requirements and reliably and effectively function as the traditional recloser.
Working & Environmental Conditions - Vacuum Circuit Breaker
1. Surrounding air temperature: -40°C~+55°C, daily temperature difference: 25°C
2. Altitude: lower than 2000m
3. Wind pressure: smaller than 700Pa (equals to wind speed 35m/s)
4. No regular dramatic shake, earthquake intensity should smaller than 8 degree.
5. No strong corrosion gas or medium (such as acids, alkali and heavy smoke )
6. Anti-filthy rank: Ⅳ
Technical Parameters - Vacuum Circuit Breaker
Table I
| Order | Name | Unit | Parameter | ||
| 1 | Rated voltage | KV | 12 | ||
| 2 | Rated current | A | 630 | ||
| 3 | Rated frequency | Hz | 50 | ||
| 4 | Imin work frequency voltage tolerance | Dry test | KV | 42/49 | |
| Wet test | 34 | ||||
| 5 | Lightening impact current tolerance (peak value) alternated, towards the ground/fracture | KV | 75/85 | ||
| 6 | Rated short circuit breaking current | KA | 20 | ||
| 7 | Rated short circuit closing current (peak value) | KA | 50 | ||
| 8 | Rated peak value current tolerance | KA | 50 | ||
| 9 | 4S short term current tolerance | KA | 20 | ||
| 10 | Rated operation cycle | Open-0.3s-slose-open-180s-close-open | |||
| 11 | Rated times of short circuit breaking current | Times | 30 | ||
| 12 | Mechanical life span | Times | 30000 | ||
| 13 | Secondary circuit I min work frequency voltage tolerance | KV | 2 | ||
| 14 | Protection CT | Ratio | A | ( )/5 | |
| Capacity | VA | 15 | |||
| 15 | Weight | Kg | 180 | ||
Table II
| Order | Name | Unit | Parameter |
| 1 | Contact openness size | Mm | 11±1 |
| 2 | Contact excess travel | Mm | 3+1.0-0.3 |
| 3 | Average Switch closing speed | M/s | 0.65±0.15 |
| 4 | Average Switch opening speed | M/s | 1.1±0.2 |
| 5 | Differences of three-phase Switch opening at the same period | Ms | ≤2 |
| 6 | Switch closing and bouncing time | Ms | ≤2 |
| 7 | Switch closing time | Ms | ≤60 |
| 8 | Switch opening time | Ms | ≤70 |
| 9 | DC resistance of each phase circuit | µΩ | ≤200 |
| 10 | Dynamic, static contacts allowed accumulated attrition thickness | Mm | 3 |