Indoor High Voltage Vacuum Circuit Breaker - Electrical Switch
Introduction - Indoor High Voltage Vacuum Circuit Breaker 1. ZN85-40.5 Series Indoor High Voltage Vacuum Circuit Breaker is an indoor device of three-phase AC 50Hz 40.5kV rated voltage and configured with special 3AV3 spring actuator. The circuit breaker can be adopted in JYN1-10.5(Z) removal-type metal closed Switchgear and KYN61-40.5 assembled metal closed Switchgear. It is the most ideal circuit breaker of 40.5 KV devices. The series products have high parameters, strong breaking ability and reliable actions. It is of stable performance, long life span, and easy maintenance and without explosion or pollution danger. It is applied to the protection and control of single generatrix system electrical facilities in industrial and mining enterprises, power plants and substations. It also can be used in other frequently operated places as well as closing capacitor groups.2. The product adopts integrated and modularized design which has reasonable simple structure. The arc chamber is on the upper side and the interlock as well as actuator is below. The 3AV3 spring actuator works stably and reliably without any adjustment. The vacuum arc chamber is in the closed insulation cylinder which reduces the overall dimension. Working & Environmental Conditions - Indoor High Voltage Vacuum Circuit Breaker
1. Environmental temperature: Maximum +40 °C, minimum -15 °C (General), and -25 °C (Alpine region);
2. Humidity: Daily average relative humidity <95%, Daily steam pressure < 2.2kPa, monthly average relative humidity < 90%, monthly steam pressure <1.8kPa
3. Altitude: ≤1000m
4. Earthquake intensity < 8°
5. No flammable, explosive, dangerous chemical corrosion or dramatic shake.
Model Meaning
Technical Parameters - Indoor High Voltage Vacuum Circuit Breaker
| Name | Unit | Parameter | |
| Rated voltage | KV | 40.5 | |
| Rated current | A | 1600 | |
| Rated insulation level | 1 min work frequency voltage tolerance | KV | 95 |
| Rated lightening impact current tolerance | 185 | ||
| Rated frequency | Hz | 50 | |
| Rated short term current tolerance | KA | 31.5 | |
| Rated peak value current tolerance | KA | 80 | |
| Rated duration time of short circuit current | S | 4 | |
| Rated short circuit breaking current | KA | 31.5 | |
| Rated short circuit closing current | KA | 80 | |
| Rated operation sequence | O-0.3s-CO-180s-CO | ||
| Opening time | Ms | <80 | |
| Rated breaking times of short circuit current | Times | 20 | |
| Rated cable charge breaking current | A | 50 | |
| Rated operation voltage | V | -110/~110,-220/~220 | |
| Mechanical life span | Times | 10000 | |
Mechanical Features - Indoor High Voltage Vacuum Circuit Breaker
| Name | Unit | Parameter |
| Contact openness size | Mm | 22±2 |
| Contact excess travel | Mm | 3.5±0.5 |
| Allowed accumulated attrition thickness | Mm | 3 |
| Average Switch closing time | M/s | 0.65±0.15 |
| Average Switch opening time (contact opens 12mm) | M/s | 1.8±0.2 |
| Closing switch and bouncing time | S | ≤0.002 |
| Time differences of three-phase closing switch in the same period | S | ≤0.002 |
| Time differences of three-phase opening switch in the same period | S | ≤0.002 |
| Contact bounce amplitude of opening the switch | Mm | 2 |
| Resistance of each circuit phase (not includes contact arm) | μΩ | ≤40 |


Picture1: Contour Dimensions of the Circuit Breaker Installed With MKYN61-40.5(Z)
Picture2: Contour Dimensions of the Circuit Breaker Installed With MJYN1-40.5(Z) Back


Complete set switchgear-Power Control System