High Voltage Electric Components - High Voltage Vacuum Circuit Breaker

Indoor AC High Voltage Vacuum Circuit Breaker

Indoor AC High Voltage Vacuum Circuit Breaker - Electrical Switch

Introduction - AC High Voltage Vacuum Circuit Breaker
MZ63A-12(VS1) Indoor AC High Voltage Vacuum Circuit Breaker applies to three-phase 50Hz, 7.2KV~12KV rated voltage power system. It is widely used in various loads of different properties and frequently operated places. It protects and controls the electrical devices in industrial mining enterprises, power plants and substation. It can configure KYN28A-12(GZS1) mid-insert handcart type Switchgear and XGN-□ fixed Switchgear. It meets national standards of GB1984 “AC High Voltage Circuit Breaker” , JB3855 “3.6~40.5KV Indoor AC High Voltage Vacuum Circuit Breaker” and IEC60056 “High Voltage AC Circuit Breaker” as well as DL/T403 Order Technical Conditions of 10~35KV Indoor AC High Voltage Vacuum Circuit Breaker .

Working & Environmental Conditions - AC High Voltage Vacuum Circuit Breaker
1. Altitude: ≤1000m
2. Environmental temperature: Maximum +40 °C, minimum -15 °C (storage at -30°C is allowed)
3. Humidity: Daily average relative humidity ≤95%, Daily steam pressure ≤2.2×KPa, monthly average relative humidity ≤90%, monthly steam pressure ≤1.8×KPa

Model Meaning
Main Technical Parameters - ZN63A-12(VSI) Vacuum Circuit Breaker
Name Unit Data
Rated voltage KV 12 12 12 12 12
Rated frequency HZ 50 50 50 50 50
Rated current A 630, 1250 630, 1250 630, 1250, 1600 1250, 1600, 2000 2000, 2500, 3150
Rated insulation level 1 min work frequency voltage tolerance KV 42 42 42 42 42
Rated lightening impact current tolerance 75 75 75 75 75
Rated short circuit breaking current KA 16 20 25 31.5 40
Rated short circuit closing current (peak value) 40 50 63 80 100
Rated peak value current tolerance 40 50 63 80 100
Rated short term current tolerance 16 20 25 31.5 40
Rated times of short term breaking current 50 50 50 50 30
Rated duration time of short circuit current Second 4 4 4 4 4
(1min)secondary circuit work frequency voltage tolerance V 2000 2000 2000 2000 2000
Rated operation sequence O4-CO4′-CO
Mechanical life span 30000 30000 30000 30000 10000
*16KA, 20KA, 25KA, 31.5KA;T′=180S;40KA:T=180S, T′=180S

Mechanical Feature Parameters - ZN63A-12(VSI) Vacuum Circuit Breaker

name
Unit Data
Contact openness size Mm 11±1 11±1 11±1 11±1 11±1
Contact excess travel Mm 3±0.5 3±0.5 3±0.5 3±0.5 3±0.5
Different periods of three-phase opening and closing switch Ms ≤2 ≤2 ≤2 ≤2 ≤2
Closing switch and bouncing time Ms ≤2 ≤2 ≤2 ≤2 ≤2
Central distance Mm 210±1.5 10±1.5 10±1.5 10±1.5 10±1.5
Switch closing contact pressure N 16 KA 20 KA 25 KA 31.5 KA 40KA
2000±200 2400±200 2400±200 3100±200 4250±250
Average Switch opening time M/s 1.1±0.2
Average Switch closing time M/s 0.6±0.2
Opening the switch, when the operation pressure is Maximum Ms ≤50
Rated ≤60
Minimum ≤60
Switch closing time Ms ≤100
Dynamic, static contact allowed accumulated attrition thickness Mm 3
Resistance of main circuit μΩ 630A
1250A
1600-2000A
2500-3150A
4000A
≤50μΩ
≤45μΩ
≤35μΩ
≤25μΩ
≤20Μω
Energy storage electrical stable power W 70(40KA 100W)
Energy storage time S <10
Technical Data - switch opening and closing coils
Switch opening coil Switch closing coil Note
Rated operation voltage(V) DC220, DC110;AC220, AC110 DC220, DC110;AC220, AC110 Do not open the switch if the Switch opening coil is smaller than 30% stable operation voltage
Coil power(W) 245 245
Normal work voltage range 65%~120%rated voltage 85%~110% rated voltage
Contour & Installation Dimensions

Note: These parameters are from ZN63A-12/□-40KA
Back