The cabinet is double-bended by the 1.5/2.0mm thick aluminum- zinc steel plate, which is light and solid. All components are connected by rivets or screws. The cabinet rear is pressed by the cover board and supported by the rivets below. In this way, in case of accident we can make sure that the leasing gas is released from the rear. The cover board on the cabinet is fixed by M6 screw.  The cabinet gate is of special design so that it can bear possible pressure released by internal breakdown caused arc burning. It can be lifted and make anti-clockwise rotation by the gate handles.  The small standard auxiliary components chamber on the upper cabinet can install terminal strip and other secondary parts. If the small chamber was lifted, the relay and other parts can be installed.  Interlock load switch and grounded switch are automatic. Grounded switch and the interlock between the cabinet gates are mandatory. Do as the following steps to achieve automatically interlock. Close the cabinet gate. Open the grounded switch and close the load switch. Separate operation mode can effectively avoid misuse.
Model Meaning - High Voltage switchgear

Technical Parameters - High Voltage switchgear
Rated voltage (kV) 12
Rated lightening impact voltage tolerance Alternately and relatively (kV) 75
Between fractures (kV) 85
One minute frequency voltage tolerance Alternately and relatively (kV) 42
Between fractures (kV) 48
Rated frequency (Hz) 50 /60
Rated current Main busbar (A) 630
Branch busbar (A) 630
Rated short-term current tolerance Main loop (kA) 20/3S
Ground loop (kA) 20/3S
Rated peak value current tolerance (kA) 50
Current transfer (A) 1700
Protection rank IP2X
Mechanical life of the load switch Times 2000
Mechanical life of ground switch Times 2000
Load switch cabinet Width (mm) 375, 500, 750
Depth (mm) 917, 940
Height (mm) 1635, 1885
Low voltage room Height (mm) 350, 450
Circuit breaker cabinet Width (mm) 750, 800
Depth (mm) 917, 940, 1245
Height (mm) 1885
Cable ditch, cable connection and size   The cabinet needs four M10 screws to be fixed with the foundation which suits all standard functional units. The cable ditch displayed is of maximum size and corresponding amendments can be made in accordance with the cable.