Complete set Switchgear- Power Control System - Low Voltage switchgear

MNS Low Voltage switchgear, Vacuum Circuit Breaker

Drawer Type - MNS Low Voltage switchgear - There are five standard sizes which are based on the height of 8E (200mm)
- 8E/4: assemble four drawer units at the height of 8E
- 8E/2: assemble two drawer units at the height of 8E
- 8E: assemble one drawer unit at the height of 8E
- 16E: assemble one drawer unit at the height of 16E (400mm)
- 24E: assemble one drawer unit at the height of 24E (600mm)

PS: Five kinds of drawers can be assembled in a single cabinet or mixed. Maximum drawer unit quantity of single assembly in one box is illustrated below:
Drawer Type 8E/4 - 8E/2 - 8E - 16E - 24E
Maximum unit capacity 36 - 18 - 9 - 4 - 3


Structure - Low Voltage switchgear
The basic structure of switchgear is constructed by the C-shaped molding material, which is bended by the steel plate with E=25mm modulus installation hole. The entire framework and inner separation board are galvanized. Imported high quality aluminum-zinc steel plate can be considered in case of special order. The surrounding gate panel and side bars are powder coated.
Design of Separated District
MNS Low Voltage switchgear can be assembled into one-side or two-side operation box. Each box is divided into three small rooms, namely: main generatrix room, electric components room and cable room.
Details - Low Voltage switchgear

Power center box
Height Width Depth Note
Hmm Bmm Tmm - Tmm1 - Tmm2
2200 400 1000 - 800 - 200 Main generatrix transfer
2200 600 1000 - 800 - 200 CW1-2000A and above
2200 800 1000 - 800 - 200 CW1-3200A and above
2200 1000 1000 - 800 - 200 CW1-4000A and above
2200 1200 1000 - 800 - 200 CW1-5000A and above

Motor control center (MCC) box - Low Voltage switchgear
Height Width Depth Note
Hmm Bmm - Bmm1 -bmm2 Tmm - Tmm1- Tmm2
2200 1000 - 600 - 400 600 - 400 - 200 One-side operation
2200 1000 - 600 - 400 1000 - 400 - 200 Two-side operation
Installation Diagram - Low Voltage switchgear [Electrical Switch] Order Information - Low Voltage switchgear
The following materials should be provided in the order:
- primary circuit programme NO., equipment model, capacity and first system diagram, Secondary circuit schematic diagram. ( If not provided, the manufacturer will conform to the standards)
- Switchgear arrangement diagram and layout plans. Model specifications of main generatrix. ( If not provided, the manufacturer will conform to the standards)
- Color of the Switchgear surface (the manufacture standard color is: light tan)
Special needs please consult with us.