GCK Low Voltage switchgear, Vacuum Circuit Breaker
1. Installation size & Mounting holes - GCK Low Voltage switchgear| Width (A) | Depth(B) | Mounting holedistance(a) | Mounting hole distance(b) |
| 600 | 600 | 485 | 485 |
| 600 | 800 | 485 | 685 |
| 600 | 1000 | 485 | 885 |
| 800 | 800 | 685 | 685 |
| 800 | 1000 | 685 | 885 |
| 1000 | 800 | 885 | 685 |
| 1000 | 1000 | 885 | 885 |
Electrical Parameters of GCK Low Voltage switchgear [Power Control System]
| Rated working frequency (HZ) | 50 | 60 |
| Rated working voltage (V) | 380 | 660 |
| Rated insulation voltage (V) | 660 | |
| Rated working current (A) | Horizontal generatrix 630, 4000 | Vertical generatrix 600, 1000 |
| Rated short-term current tolerance | Horizontal generatrix 80KA (RMS)/1s | |
| Vertical generatrix 50 KA (RMS)/1s | ||
| Main circuit connector (A) | 200, 400, 630 | |
| Auxiliary circuit connector (A) | 10 | |
| Working frequency voltage tolerance per minute (V) | 2500 | |
| Maximum capacity of motor control (KW) | 155 | |
| Protection rank | IP40/IP30 | IP30 |
| Operation mode | Local, remote, automatic | |
1. Dimension of PC Switchgear2. Dimension of MCC Switchgear (not on the wall)
Order Information - GCK Low Voltage switchgearThe following materials should be provided in the order:
1. primary circuit programme NO.
2. Equipment model
3. Capacity and single wire system diagram
4. Secondary circuit schematic diagram. (If not provided, the manufacturer will conform to the standards.)
5. Switchgear arrangement diagram and layout plans
6. Model specifications of main generatrix. ( If not provided, the manufacturer will conform to the standards.)
7. Color of the Switchgear surface (the manufacture standard color is: light tan)
PS. Special needs please consult with us.
Honorable Project of Shanghai Golden Bell Electric Group Co., Ltd. --- Yunnan Kunming Airport
2 1 Back