Complete set Switchgear- Power Control System - Low Voltage switchgear [ Electrical Switch ]

GCK Low Voltage switchgear, Vacuum Circuit Breaker

1. Installation size & Mounting holes - GCK Low Voltage switchgear
Width (A) Depth(B) Mounting holedistance(a) Mounting hole distance(b)
600 600 485 485
600 800 485  685
600 1000 485 885
800 800 685 685
800 1000 685 885
1000 800 885 685
1000 1000 885 885

Electrical Parameters of GCK Low Voltage switchgear [Power Control System]
Rated working frequency (HZ) 50 60
Rated working voltage (V) 380 660
Rated insulation voltage (V)  660
Rated working current (A) Horizontal generatrix 630, 4000 Vertical generatrix 600, 1000
Rated short-term current tolerance Horizontal generatrix 80KA (RMS)/1s
Vertical generatrix 50 KA (RMS)/1s
Main circuit connector (A) 200, 400, 630
Auxiliary circuit connector (A) 10
Working frequency voltage tolerance per minute (V) 2500
Maximum capacity of motor control (KW) 155
Protection rank IP40/IP30 IP30
Operation mode Local, remote, automatic
Dimensions - GCK Low Voltage switchgear

1. Dimension of PC  Switchgear2. Dimension of MCC Switchgear (not on the wall)

Note: 1840 dimension district is functional unit district. Order Information - GCK Low Voltage switchgear
The following materials should be provided in the order:
1. primary circuit programme NO.
2. Equipment model
3. Capacity and single wire system diagram
4. Secondary circuit schematic diagram. (If not provided, the manufacturer will conform to the standards.)
5. Switchgear arrangement diagram and layout plans
6. Model specifications of main generatrix. ( If not provided, the manufacturer will conform to the standards.)
7. Color of the Switchgear surface (the manufacture standard color is: light tan)
PS. Special needs please consult with us.

Honorable Project of Shanghai Golden Bell Electric Group Co., Ltd. --- Yunnan Kunming Airport
2 1 Back